The Standards of "Leak testing of Valves"
The Standards of "Leak testing of Valves"
¶ American Petroleum Institute API¶
The API standard 598.. Valve Inspection and Testing, covers the testing and inspection requirements for gate, globe, check, ball, plug and butterfly valves. It has acceptable leakage rates for liquid as well as gas testing. All valves built to the various API standards are required to meet API-598 leakage criteria prior to shipment from the manufacturer or supplier.
API 598 states for shell and BACK SEAT tests, no visible leakage is permitted. If the fluid is a liquid, there shall be no visible evidence of drops or wetting of the external surfaces (no visible leakage through the body, body liner, if any, and body-to-bonnet joint and no structural damage).
If the test fluid is air or gas, no leakage shall be revealed by the established detection method. For both the low-pressure closure test and the high-pressure closure test, visual evidence of leakage through the disk, behind the seat rings, or past the shaft seals (of valves that have this feature) is not permitted (Plastic deformation of resilient seats and seals is not considered structural damage). The allowable rate for leakage of test fluid past the seats, for the duration of the tests, is listed in the following table..
Valve Size NPS |
All Resilient Seated Valves |
All Metal Seated Valves (except Check Valves) |
|
Liquid Test (drops min.) |
Gas Test (bubbles min.) |
||
< 2 | 0 | 0 (1) | 0 (1) |
2 - 6 | 0 | 12 | 24 |
8 - 12 | 0 | 20 | 40 |
> 12 | 0 | 28 | 56 |
Valve Size NPS |
All Resilient Seated Valves |
Metal Seated Check Valves |
|
Liquid Test (drops min.) |
Gas Test (bubbles min.) |
||
< 2 | 0 | (2) | (3) |
2 - 6 | 0 | (2) | (3) |
8 - 12 | 0 | (2) | (3) |
> 12 | 0 | (2) | (3) |
General notes..
- 1 milliliter is considered equivalent to 16 drops.
- For check valves larger than NPS 24, the allowable leakage rate
shall be per agreement between purchaser and manufacturer.
Notes..
- There shall be no leakage for the minimum specified test duration. For liquid test, 0 drop means no visible leakage per minimum specified test duration. For gas test, 0 bubble means less then 1 bubble per minimum specified test duration.
- The maximum permissible leakage rate shall be 0.18 cubic inch (3 cubic centimeters) per minute per inch of nominal pipe size.
- The maximum permissible leakage rates shall be 1.5 standard cubic feet (0.042 cubic meter) of gas per hour per inch of nominal pipe size.
¶ Manufacturer's Standardisation Society MSS¶
The MSS standard MSS-SP-61.. Pressure Testing of Valves was originally adopted in 1961. It was developed for the purpose of providing a uniform means of testing valves commonly used in the "full open" and "full closed" type of service. It is not intended for use with control valves. Refer to standard ANSI/FCI 70-2 for Control Valves.
Section 5 of their Pressure Testing of Steel Valves, relates to seat closure tests, and defines the following leakage rates..
- Gate, Globe, Ball valves..
10 cc/hr per inch of nominal pipe diameter. (Example.. A 6" globe valve is allowed to leak 60 cc/hr in a test) - Check valves..
40 cc/hr per inch of nominal pipe diameter
All shutoff or isolation valves specified to MSS-SP-61 must pass the above standards. The seat closure test must be performed at a fluid (liquid or gas) pressure no less than 1.1 times the 1000°F (380°C) rating rounded to the next 5 psi (0.5 bar).
¶ American National Standards Institute ANSI¶
The ANSI standard FCI 70-2.. Control Valve Seat Leakage, establishes a series of six seat leakage classes for control valves and defines the test procedures.
Class I. Is also know as dust tight and can refer to metal or resilient seated valves.
Class II. This class establishes the maximum permissible leakage generally associated with commercial double-seat control valves or balanced single-seat control valves with a piston ring seal and metal-to-metal seats.
Class III. This class establishes the maximum permissible leakage generally associated with Class II (4.2.2), but with a higher degree of seat and seal tightness.
Class IV. This class establishes the maximum permissible leakage generally associated with commercial unbalanced single-seat control valves and balanced single-seat control valves with extra tight piston rings or other sealing means and metal-to-metal seats.
Class V. This class is usually specified for critical applications where the control valve may be required to be closed, without a blocking valve, for long periods of time with high differential pressure across the seating surfaces. It requires special manufacturing, assembly and testing techniques. This class is generally associated with metal seat, unbalanced single-seat control valves or balanced single-seat designs with exceptional seat and seal tightness.
CLASS VI. This class establishes the maximum permissible seat leakage generally associated with resilient seating control valves either unbalanced or balanced single-seat with "O" rings or similar gapless seals.
Leakage Class |
Maximum Leakage Allowable |
Test Medium |
I | ||
II | 0.5% of rated capacity | Air or water at 50-125°F (10-52°) |
III | 0.1% of rated capacity | As above |
IV | 0.01% of rated capacity | As above |
V | 0.0005 ml per minute of water per inch of port diameter per psi differential | Water at 50 to 125°F (10 to 52°C) |
VI | Not to exceed amounts shown in following table based on port diameter. | Air or nitrogen at 50 to 125 F (10to52C) |
Leakage Class |
Test Pressure | Test Procedure |
I | No test required, as long as purchaser and vendor both agree. |
|
II | 45-60 psig or max. operating differential whichever is lower | Pressure applied to valve inlet with outlet open to atmosphere or connected to a low head loss measuring device full normal closing thrust provided by actuator. |
III | As above | As above |
IV | As above | As above |
V | Max service pressure drop across valve plug, not to exceed ANSI body rating. | Pressure applied to valve inlet after filling entire body cavity and connected piping with water and stroking valve plug closed. Use net specified max actuator thrust, but no more, even if available during test. Allow time for leakage flow to stabilize. |
VI | 50 psig or max rated differential pressure across valve plug whichever is lower. | Actuator should be adjusted to operating conditions specified with full normal closing thrust applied to valve plug seat. Allow time for leakage flow to stabilize and use suitable measuring device. |
CONTROL VALVE SEAT LEAKAGE CLASSIFICATIONS |
|||
Nominal Port Dia Inches |
Nominal Port Dia mm |
Leak Rate ml / min |
Leak Rate bubbles / min |
3 | 76 | 0.9 | 6 |
4 | 102 | 1.7 | 11 |
6 | 152 | 4 | 27 |
8 | 203 | 6.75 | 45 |
10 | 250 | 11.1 | |
12 | 300 | 16 | |
14 | 350 | 21.6 | |
16 | 400 | 28.4 |
¶ International organization for standardization ISO
The purpose of ISO standard 5208.. Industrial valves - Pressure testing of metallic valves, is the establishment of basic requirements and practices for pressure testing valves of various configurations that are used in general purpose, power generation, petroleum, and petrochemical or allied industry applications. The intent is to provide a consistent set of procedural requirements and acceptance criteria that can be considered in conjunction with valve specific standards appropriate for specific applications. Account has been taken of the valve testing requirement needs of EN 12266 and API 598 with requirements referenced for PN designated valves for the former and Class designated valves for the latter.
Prescribed pressure tests |
|||
TEST | DN | PN OR CLASS |
GLOBE VALVE |
SHELL TEST LIQUID |
ALL | ALL | REQ |
SHELL TEST GAS |
ALL | ALL | OPT |
BACK SEAT TEST (B, C) LIQUID |
ALL | ALL | OPT |
CLOSURE TEST GAS LOW-PRESSURE |
DN ≤ 100 | CLASS ≤ 1500 AND PN ≤ 250 |
OPT |
CLASS > 1500 AND PN > 250 |
OPT | ||
DN > 100 | CLASS ≤ 600 AND PN ≤ 100 |
OPT | |
CLASS > 600 AND PN > 100 |
OPT | ||
CLOSURE TEST LIQUID HIGH-PRESSURE |
DN ≤ 100 | CLASS ≤ 1500 AND PN ≤ 250 |
REQ |
CLASS > 1500 AND PN > 250 |
REQ | ||
DN > 100 | CLASS ≤ 600 AND PN ≤ 100 |
REQ | |
CLASS > 600 AND PN > 100 |
REQ | ||
Prescribed pressure tests |
|||
TEST | DN | PN OR CLASS |
PLUG VALVE (A) |
SHELL TEST LIQUID |
ALL | ALL | REQ |
SHELL TEST GAS |
ALL | ALL | OPT |
BACK SEAT TEST (B, C) LIQUID |
ALL | ALL | NOT REQ |
CLOSURE TEST GAS LOW-PRESSURE |
DN ≤ 100 | CLASS ≤ 1500 AND PN ≤ 250 |
REQ |
CLASS > 1500 AND PN > 250 |
OPT | ||
DN > 100 | CLASS ≤ 600 AND PN ≤ 100 |
OPT | |
CLASS > 600 AND PN > 100 |
OPT | ||
CLOSURE TEST LIQUID HIGH-PRESSURE |
DN ≤ 100 | CLASS ≤ 1500 AND PN ≤ 250 |
OPT |
CLASS > 1500 AND PN > 250 |
REQ | ||
DN > 100 | CLASS ≤ 600 AND PN ≤ 100 |
OPT | |
CLASS > 600 AND PN > 100 |
REQ | ||
Prescribed pressure tests |
|||
TEST | DN | PN OR CLASS |
CHECK VALVE |
SHELL TEST LIQUID |
ALL | ALL | REQ |
SHELL TEST GAS |
ALL | ALL | OPT |
BACK SEAT TEST (B, C) LIQUID |
ALL | ALL | NOT REQ |
CLOSURE TEST GAS LOW-PRESSURE |
DN ≤ 100 | CLASS ≤ 1500 AND PN ≤ 250 |
OPT |
CLASS > 1500 AND PN > 250 |
OPT | ||
DN > 100 | CLASS ≤ 600 AND PN ≤ 100 |
OPT | |
CLASS > 600 AND PN > 100 |
OPT | ||
CLOSURE TEST LIQUID HIGH-PRESSURE |
DN ≤ 100 | CLASS ≤ 1500 AND PN ≤ 250 |
REQ |
CLASS > 1500 AND PN > 250 |
REQ | ||
DN > 100 | CLASS ≤ 600 AND PN ≤ 100 |
REQ | |
CLASS > 600 AND PN > 100 |
REQ | ||
Prescribed pressure tests |
|||
TEST | DN | PN OR CLASS |
FLOATING BALL OR DIAPHRAGM VALVE |
SHELL TEST LIQUID |
ALL | ALL | REQ |
SHELL TEST GAS |
ALL | ALL | OPT |
BACK SEAT TEST (B, C) LIQUID |
ALL | ALL | NOT REQ |
CLOSURE TEST GAS LOW-PRESSURE |
DN ≤ 100 | CLASS ≤ 1500 AND PN ≤ 250 |
REQ |
CLASS > 1500 AND PN > 250 |
REQ | ||
DN > 100 | CLASS ≤ 600 AND PN ≤ 100 |
REQ | |
CLASS > 600 AND PN > 100 |
REQ | ||
CLOSURE TEST LIQUID HIGH-PRESSURE |
DN ≤ 100 | CLASS ≤ 1500 AND PN ≤ 250 |
OPT |
CLASS > 1500 AND PN > 250 |
OPT | ||
DN > 100 | CLASS ≤ 600 AND PN ≤ 100 |
OPT | |
CLASS > 600 AND PN > 100 |
OPT |
Notes..
- REQ - REQUIRED, OPT - OPTIONAL
- Successful completion of an optional test does not relieve the manufacturer from also successfully completing the required test.
- In the case of resilient seated valves, a high-pressure closure test may °rade subsequent closure sealing performance in low-pressure applications.
- (A) Plug valves that rely on a sealing compound to effect a closure seal may be closure tested with the compound installed.
- (B) Successful completion of a BACK SEAT test should not be interpreted as a recommendation by the valve manufacturer that, while an installed valve is pressurized, the stem seal may be altered, repaired or replaced when BACK SEATed.
- (C) In the case of bellows stem sealed valves, a BACK SEAT test is not required.
Maximum allowable closure test leakage rate |
|||
TEST FLUID |
UNIT LEAKAGE RATES |
RATE A |
RATE AA |
LIQUID | MM3/S | (1) | 0.006 X DN |
DROPS/S | 0.0001 X DN |
||
GAS | MM3/S | (1) | 0.18 X DN |
BUBBLES/S | 0.003 X DN |
||
Maximum allowable closure test leakage rate |
|||
TEST FLUID |
UNIT LEAKAGE RATES |
RATE B |
RATE C |
LIQUID | MM3/S | 0.01 X DN |
0.03 X DN |
DROPS/S | 0.00016 X DN |
0.0005 X DN |
|
GAS | MM3/S | 0.3 X DN |
3 X DN |
BUBBLES/S | 0.0046 X DN |
0.0458 X DN |
|
Maximum allowable closure test leakage rate |
|||
TEST FLUID |
UNIT LEAKAGE RATES |
RATE CC |
RATE D |
LIQUID | MM3/S | 0.08 X DN |
0.1 X DN |
DROPS/S | 0.0013 X DN |
0.0016 X DN |
|
GAS | MM3/S | 22.3 X DN |
30 X DN |
BUBBLES/S | 0.3407 X DN |
0.4584 X DN |
|
Maximum allowable closure test leakage rate |
|||
TEST FLUID |
UNIT LEAKAGE RATES |
RATE E |
RATE EE |
LIQUID | MM3/S | 0.3 X DN |
0.39 X DN |
DROPS/S | 0.0048 X DN |
0.0062 X DN |
|
GAS | MM3/S | 300 X DN |
470 X DN |
BUBBLES/S | 4.5837 X DN |
7.1293 X DN |
|
Maximum allowable closure test leakage rate |
|||
TEST FLUID |
UNIT LEAKAGE RATES |
RATE F |
RATE G |
LIQUID | MM3/S | 1 X DN |
2 X DN |
DROPS/S | 0.016 X DN |
0.032 X DN |
|
GAS | MM3/S | 3000 X DN |
6000 X DN |
BUBBLES/S | 45.837 X DN |
91.673 X DN |
|
Maximum allowable closure test leakage rate |
|||
TEST FLUID |
UNIT LEAKAGE RATES |
RATE F |
RATE G |
LIQUID | MM3/S | 1 X DN |
2 X DN |
DROPS/S | 0.016 X DN |
0.032 X DN |
|
GAS | MM3/S | 3000 X DN |
6000 X DN |
BUBBLES/S | 45.837 X DN |
91.673 X DN |
Notes..
(1) No visually detectable leakage for the duration of the test
- The leakage rates only apply when discharging test fluid to the atmosphere.
- The closure leakage rate that applies is either that identified in a valve product standard or a leakage rate identified in a purchaser's valve procurement purchase order that is more stringent than that specified in the product standard.
- The meaning of "No visually detectable leakage" is that there is no visible weeping or leakage in the form of drops or bubbles.
- There is a loosely defined correspondence between the leakage rate acceptance values of API 598 and the leakage values Rate A as applied to DN ≤50, Rate AA-Gas and Rate CC-Liquid for other than metal seated check valves and for check valves Rate EE-Gas and Rate G-Liquid. Rates A, B, C, D E, F and G correspond to values in EN 12266-1.
Remark(s) of the Author...
Types of Leakage
There are two types of leakage from a valve, namely; fugitive emissions from the valve to atmosphere, and leakage through the valve but contained within the piping system.
Fugitive emissions can both be detrimental to the environment and a potential safety hazard. Valves are considered to be the major contributors to fugitive emission losses.
Leakage through the valve can also be a safety hazard, and can be detrimental to the process.
Reasons that Valves leak
Common causes of leakage through the valve include..
- Valve is not fully closed. This can be due to various reasons, including;
- Valve seat is prevented from closing fully due to dirt, rust, or line debris
- Insufficient actuator travel
- The seat is damaged, e.g. scored
- The seal is damaged
Common causes of leakage to atmosphere..
- Gasket between valve-body and valve-bonnet is damaged
- Stem Pakking is worn, loose or damaged
Both of them can have several causes