Ammete China Water Meter
Price: Contact
The Woltman Type Water Meter delivers precise, high-volume flow measurement for demanding industrial and commercial applications, with stable performance and minimal pressure loss.
Product Description
Application:
The Woltman Type Water Meter delivers precise, high-volume flow measurement for demanding industrial and commercial applications, with stable performance and minimal pressure loss.
Key Features:
• Removable Mechanism: Easy maintenance without removing the body.
• Woltman Precision: High flow capacity with minimal pressure loss.
• Sealed Register: Dry-dial counter stays clear and fog-free.
• Industrial Strength: Robust cast iron body with epoxy coating.
• Interchangeable Parts: Standardized components for easy replacement.
• Low Pressure Loss: Optimized flow design to minimize energy costs and pumping pressure.
• High Flow Capacity: Handles heavy-duty industrial loads and peak flow surges reliably.
• Pulse Ready: Pre-equipped for reed switch or inductive pulse output.
Specifications:
• Body material: Cast iron
• Accuracy: R50/ R80/ R100
• Size: DN50-65-80-100-125-150-200-250-300
• Cold water: 0 ℃ - 50℃
• Hot water: 0 ℃ - 90℃
• Water pressure: 1.0MPa / 1.6MPa
• △P≤63
• Flange connecting option: ISO/ DIN/ ANSI
• Pulse output option: 1P=100-1000L
• Register: Full glass sealed/ Plastic-sealed
Installation:
• Best installed horizontally with the register facing up for maximum accuracy.
• Maintain 10×DN upstream and 5×DN downstream to ensure stable water flow.
• Water must flow strictly in the direction of the arrow cast on the body.
Accuracy:
• From minimum flow rate (Q1) inclusive, to transitional flow rate (Q2) exclusive: ±5%
• From transitional flow rate (Q2) inclusive, to overload flow rate (Q4) exclusive: ±2%
• Hot water meter ±3%
Technical Data:
|
Model |
Unit |
AMT IW-F |
AMT IW-G |
AMT IW-H |
AMT IW-I |
AMT IW-J |
AMT IW-K |
AMT IW-L |
AMT IW-M |
AMT IW-N |
|
|
Nominal Size |
mm (inch) |
2'' |
2-1/2'' |
3'' |
4'' |
5'' |
6'' |
8'' |
10'' |
12'' |
|
|
Overload Flow Rate (Q4) |
m3h |
31.25 |
50 |
78.75 |
125 |
200 |
312.5 |
500 |
787.5 |
1250 |
|
|
Permanent Flow Rate (Q3) |
m3h |
25 |
40 |
63 |
100 |
160 |
250 |
400 |
630 |
1000 |
|
|
R=50 |
Transitional Flow Rate (Q2) |
m3/h |
0.8 |
1.28 |
2.016 |
3.2 |
5.12 |
8 |
12.8 |
20.16 |
32 |
|
Minimum Flow Rate (Q1) |
m3/h |
0.5 |
0.8 |
1.26 |
2 |
3.2 |
5 |
8 |
12.6 |
20 |
|
|
R=80 |
Transitional Flow Rate (Q2) |
m3/h |
0.5 |
0.8 |
1.26 |
2 |
3.2 |
5 |
8 |
12.6 |
20 |
|
Minimum Flow Rate (Q1) |
m3/h |
0.3125 |
0.5 |
0.787 |
1.25 |
2 |
3.125 |
5 |
7.875 |
12.5 |
|
|
R=100 |
Transitional Flow Rate (Q2) |
m3/h |
0.4 |
0.64 |
1.008 |
1.6 |
2.56 |
4 |
6.4 |
10.08 |
16 |
|
Minimum Flow Rate (Q1) |
m3/h |
0.25 |
0.4 |
0.63 |
1 |
1.6 |
2.5 |
4 |
6.3 |
10 |
|
|
Temperature class |
T °C |
T50/T90 |
|||||||||
|
Water pressure class |
MPa |
1.0/1.6 |
|||||||||
|
Pressure-loss class |
|
△P63 |
|||||||||
|
Installation Positions |
|
HORIZONTAL |
|||||||||
Dimension:
|
Model |
Nominal Size (mm) |
Size (inch) |
Length (mm) |
Height (mm) |
Outside diameter D (mm) |
Bolt circle Dia D1 (mm) |
Connecting Bolt (n-Md) |
PCS/ CTN |
Carton Weight (KG) |
|
AMT IW-F |
50 |
2'' |
200 |
220 |
165 |
125 |
4-M16 |
1 |
10.87 |
|
AMT IW-G |
65 |
2-1/2'' |
200 |
225 |
185 |
145 |
4-M16 |
1 |
13 |
|
AMT IW-H |
80 |
3'' |
225 |
280 |
200 |
160 |
8-M16 |
1 |
14.55 |
|
AMT IW-I |
100 |
4'' |
250 |
290 |
220 |
180 |
8-M16 |
1 |
16.08 |
|
AMT IW-J |
125 |
5'' |
250 |
300 |
250 |
210 |
8-M16 |
1 |
30 |
|
AMT IW-K |
150 |
6'' |
300 |
320 |
285 |
240 |
8-M20 |
1 |
24.77 |
|
AMT IW-L |
200 |
8'' |
350 |
345 |
340 |
295 |
8-M20 (1.0Mpa) |
1 |
45 |
|
12-M20 (1.6Mpa) |
1 |
||||||||
|
AMT IW-M |
250 |
10'' |
450 |
435 |
395 (1.0Mpa) |
350 (1.0Mpa) |
12-M20 (1.0Mpa) |
1 |
67 |
|
405 (1.6Mpa) |
355 (1.6Mpa) |
12-M24 (1.6Mpa) |
1 |
||||||
|
AMT IW-N |
300 |
12'' |
500 |
460 |
445 (1.0Mpa) |
400 (1.0Mpa) |
12-M20 (1.0Mpa) |
1 |
97 |
Related projects




.png)